Example: Chart Record Process Display Value (0 to 10 VDC):
The process range is 300-700. Programming 300 for ANLO (0 VDC
value) and 700 for ANHI (10 VDC value) yields full scale deflection for a
chart recorder (0 to 10 VDC). The 0 to 10 VDC output is assigned to
transmit the input reading (ANAS = INP).
Example: Linear Control Output (4 to 20 mA):
A linear DC input power control unit is used for process control. An
outputcontroldeadband of ±2.0% and anoutputupdate time of10 seconds
is desired. The following set-up values illustrate the configuration:
ANAS = OP
ANLO = 0.0%
ANHI = 100.0%
ANdb = 2.0%
ANUt = 10 seconds
LOCKOUTS MODULE (3-LC)
The controller can be programmed to limit operator access to various
parameters, control modes, and display contents. The configuration of the
lockouts is grouped into three sections: Lower Display Lockouts, Protected
Mode Lockouts and Hidden Mode Lockouts.
Lower Display Lockouts (SP, OP, IN-2, dEv, bdSP)
Thecontentsofthesecondarydisplaycanbechangedinthenormaldisplay
mode by successively pressing the DSP button. This action scrolls through
the possible display parameters, when enabled.
The parameters can be set for one of the following:
LOC (Lockout) – Prevents the parameter from appearing in the
secondary display.
rEd (Read only) – Parameter appears, but cannot be modified.
Ent (Entry) – Parameter appears and can be modified.
The lower display content possibilities are:
SP – Setpoint Value
OP* – % Output Power
IN-2* – Second analog input (Remote setpoint)
dEv* – Setpoint Deviation
bdSP – Blank Display
If all parameters are set to lock “LOC”, the display remains on the last
parameter that was viewed.
*Note: These parameters are model specific and may not appear in the
programming sequence.
Note: If a parameter is active in the lower display and is then subsequently locked
out, press “DSP” once in the normal display mode to remove it from the display.
-27-
Figure 15, Linear DC Output