Red-lion TLA Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Red-lion TLA. Red Lion TLA User Manual [it] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 16
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
1
MODEL TLA - TEMPERATURE LIMIT ALARM
FM APPROVED, UL RECOGNIZED
2-LINE BY 4-DIGIT DISPLAY
EXCEED, OUTPUT, AND ALARM ANNUNCIATORS
FOUR BUTTON SILICONE RUBBER KEYPAD
THERMOCOUPLE OR RTD SENSOR INPUT
REMOTE RESET INPUT
MAIN LIMIT OUTPUT: 5A RELAY. SELECTABLE FOR HIGH OR
LOW TRIP ACTIVATION
OPTIONAL ALARMS: 5A RELAY(S)
OPTIONAL NEMA 4X/IP65 SEALED FRONT BEZEL
PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS
GENERAL DESCRIPTION
The TLA is a Factory Mutual approved temperature limit alarm, intended to
provide an independent shutdown for thermal processes. The TLA accepts
signals from a variety of temperature sensors (thermocouple or RTD elements),
and its comprehensive programming allows it to meet a wide variety of
application requirements.
Dual 4-digit displays allow viewing of the process temperature and limit
setpoint simultaneously. Front panel indicators inform the operator of the
process and output status. The main limit output and alarm outputs are field
replaceable.
The limit output is selectable for high or low trip activation. If the process
temperature goes above the limit setpoint for a high trip, or below the limit
setpoint for a low trip, the limit relay will de-energize to initiate a process
shutdown. The limit output cannot be reset until the process temperature returns
to the proper operating range; manual reset is required (local or remote). Sensor
failure will initiate a process shutdown.
Relay alarm(s) can be configured to activate according to a variety of actions
(Absolute HI or LO, Deviation HI or LO, and Band IN or OUT) with adjustable
hysteresis. A standby feature suppresses the alarm during power-up until the
process stabilizes outside the alarm region.
The unit is constructed of a lightweight, high impact plastic case with a tinted
front panel. The front panel meets NEMA 4X/IP65 specifications when properly
installed. Multiple units can be stacked horizontally or vertically. Modern
surface-mount technology, extensive testing, plus high immunity to noise
interference makes the TLA extremely reliable in industrial environments.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the TLA to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the unit.
-0.0
+0.6
-0.000
+0.024
-0.0
+0.6
-0.000
+0.024
(45 )
1.772
(45 )
1.772
(9.4)
0.37
4.17 (105.9)
1.95
1.95 (49.5)
(49.5)
EX OUTA1A2
PR
DIMENSIONS In inches (mm)
FM
APPROVED
PROCESS CONTROL EQUIPMENT
Bulletin No. TLA-B
Drawing No. LP0553
Released 06/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
PANEL CUT-OUT
UL Recognized Component,
File # E156876
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - DIMENSIONS In inches (mm)

1MODEL TLA - TEMPERATURE LIMIT ALARM  FM APPROVED, UL RECOGNIZED 2-LINE BY 4-DIGIT DISPLAY EXCEED, OUTPUT, AND ALARM ANNUNCIATORS FOUR BUTTON

Page 2 - GENERAL SPECIFICATIONS

10LIMIT OUTPUT ACTIONThe limit output is selectable for high or low trip activation. If the process temperature goes above the limit setpoint for a hi

Page 3 - EMC INSTALLATION GUIDELINES

11Alarm Reset SequenceAlarm Standby Delay SequenceONOFFALARM VALUEOFFONOFFOFFTIMEAUTOMATICRESETMANUALRESETMANUAL RESETPERFORMED BY OPERATORINPUTALARM

Page 4 - 1.0 INSTALLING THE TLA

Millivolt Calibration (CAL)Connect precision millivolt source with an accuracy of 0.03% to terminals #8 (-) & #9 (+). Cold Junction or RTD ohms ca

Page 5 - 2.0 WIRING THE TLA

13PROBLEMS POSSIBLE CAUSEREMEDIES1. Check power.2. Verify power reading.3. Check connections.4. Check installation.TLA NOT WORKING 1. Incorrect parame

Page 6 - 4.0 PARAMETER MODE

148.0 INSTALLING AN OUTPUT bOARDThe TLA is supplied with an output board installed.Replacing Output Board1. Remove the bezel assembly.2. Lift up on th

Page 7 - -999 to 9999

15This page intentionally left blank

Page 8 - * Model Number Dependent

LIMITED WARRANTYThe Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from

Page 9 - -LC Lockout Parameters

2GENERAL SPECIFICATIONS1. DISPLAY: 2 line by 4-digit LEDUpper (Main) Display: 0.4" (10.2 mm) high red LEDLower (Secondary) Display: 0.3" (7.

Page 10 - 5.0 ALARMS (OPTIONAL)

3OUTPUT SPECIFICATIONS1. LIMIT AND ALARM OUTPUT RELAYS:Contact Rating: 5 A @ 250 VAC or 30 VDC (resistive load).Life Expectancy: 100,000 cycles at max

Page 11 - Error Flag E-CL

The TLA meets NEMA 4X/IP65 requirements for indoor use to provide a watertight seal in steel panels with a minimum thickness of 0.09 inch, or aluminum

Page 12 - 6.0 CALIbRATION

52.0 WIRING THE TLAAfter the unit has been mechanically mounted, it is ready to be wired. All wiring connections are made to the rear screw terminals.

Page 13 - 7.0 TROUbLESHOOTING

63.0 FRONT PANEL DESCRIPTIONEX OUTA1A2PRILLUMINATES WHEN THE LIMIT OUTPUT IS DE-ENERGIZED.ILLUMINATES WHEN ALARM 2 IS ON.ILLUMINATES WHEN THEPROCESS T

Page 14 - 9.0 TERMINAL CONFIGURATIONS

7CONFIGURATION PARAMETER MODULESThe Configuration Parameter modules are accessed by pressing the UP button from CNFP in the Parameter Mode. The UP or

Page 15

8CONFIGURE MODULE 3 - LOCkOUT PARAMETERS (3-LC)DISPLAY PARAMETER DESCRIPTION/ COMMENTSPASSPassword 0 to 250 (10)AL *Alarms #1 and #2 access levelThe a

Page 16 - LIMITED WARRANTY

9CONFIGURE MODULE 9 - FACTORy SERvICE OPERATIONS (9-FS)DISPLAY PARAMETER RANGE DESCRIPTION/ COMMENTSCodEFactory service function code48 - Calibrate in

Commentaires sur ces manuels

Pas de commentaire