GENERAL DESCRIPTION
The G303 Operator Interface Terminal combines unique capabilities normally
expected from high-end units with a very affordable price. It is built around a
high performance core with integrated functionality. This core allows the G303
to perform many of the normal features of the Paradigm range of Operator
Interfaces while improving and adding new features.
The G303 is able to communicate with many different types of hardware using
high-speed RS232/422/485 communications ports and Ethernet 10 Base T/100
Base-TX communications. In addition, the G303 features USB for fast downloads
of configuration files and access to trending and data logging. A CompactFlash
socket is provided so that Flash cards can be used to collect your trending and data
logging information as well as to store larger configuration files.
In addition to accessing and controlling of external resources, the G303
allows a user to easily view and enter information. The unit uses a Liquid
Crystal Display (LCD) module, which is easily readable in both indoor and
outdoor applications. Users can enter data through the front panel 32-button
keypad that has user identifiable keys.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially harmful to
persons or equipment in the event of a fault to the controller.
CONTENTS OF PACKAGE
- G303 Operator Interface.
- Panel gasket.
- Two user legendable key sheets.
- Template for panel cutout.
- Hardware packet for mounting unit into panel.
- Terminal Block for connecting power.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
G303
Operator Interface for indoor applications only,
textured finish with embossed keys
G303M000
Operator Interface for indoor or outdoor
applications, glossy finish with UV rated overlay
(keys are not embossed)
G303S000
G3CF CompactFlash Card
6
G3CFxxxx
G3RS RS232/485 Optional Communication Card G3RS0000
G3CN CANopen Optional Communication Card G3CN0000
G3DN
DeviceNet Option Card With Isolated High
Speed Communications Ports
G3DN0000
G3GSM GSM/GPRS Modem Option Card
3
G3GSM000
G3PBDP Profibus DP Optional Communication Card G3PBDP00
SFCRM2 Crimson 2.0
2
SFCRM200
CBL
RS-232 Programming Cable CBLPROG0
USB Cable CBLUSB00
Communications Cables
1
CBLxxxxx
DR DIN Rail Mountable Adapter Products
4
DRxxxxxx
Replacement Battery
5
BNL20000
Key Strip Paper LBAFLM02
G3FILM Protective Films G3FILM03
1
Contact your Red Lion distributor or visit our website for complete selection.
2
Use this part number to purchase Crimson on CD with a printed
manual, USB cable, and RS-232 cable. Otherwise, download from www.
redlion.net.
3
Antenna (G3QANT00) is NOT included with the card. Must be purchased
separately if needed.
4
Red Lion offers RJ modular jack adapters. Refer to the DR literature for
complete details.
5
Battery type is lithium coin type CR2025.
6
Industrial grade two million write cycles. SMART Modular Technologies model
SG9CF (UL Listed Directory Category NWGQ)
MODEL G303 - GRAPHIC LCD OPERATOR INTERFACE TERMINALS
Bulletin No. G303-N
Drawing No. LP0561
Released 11/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
CAUTION: Risk of Danger.
Read complete instructions prior to installation
and operation of the unit.
CompactFlash is a registered trademark of CompactFlash Association.
CONFIGURED USING CRIMSON 2.0 SOFTWARE
UP TO 5 RS-232/422/485 COMMUNICATIONS PORTS
(2 RS-232 AND 1 RS-422/485 ON BOARD, 1 RS-232 AND 1
RS422/485 ON OPTIONAL COMMUNICATIONS CARD)
10 BASE T/100 BASE-TX ETHERNET PORT TO NETWORK
UNITS AND HOST WEB PAGES
USB PORT TO DOWNLOAD THE UNIT’S CONFIGURATION
FROM A PC OR FOR DATA TRANSFERS TO A PC
UNIT’S CONFIGURATION IS STORED IN NON-VOLATILE
MEMORY (4 MBYTE FLASH)
COMPACTFLASH
®
SOCKET TO INCREASE MEMORY CAPACITY
3.2-INCH 128X64 PIXEL LCD WITH YELLOW LED BACKLIGHT,
ABLE TO SUPPORT TEXT AND SIMPLE GRAPHICS
OUTDOOR UNIT WITH UV RATED OVERLAY AVAILABLE
32 BUTTON KEYPAD WITH USER IDENTIFIABLE KEYS,
NAVIGATIONAL KEYS, NUMERIC KEYS, KEYS FOR ON-SCREEN
MENUS, AND OTHER VARIOUS KEYS.
THREE FRONT PANEL LEDS
POWER UNIT FROM 24 VDC ±20% SUPPLY
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
Class II, Division 2, Groups F and G
Class III, Division 2
C
US LISTED
U
L
R
63YN
LABORATORY EQUIPMENT
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2/CLASS II, DIVISION 2/CLASS III, DIVISION 2
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - ORDERING INFORMATION

1GENERAL DESCRIPTIONThe G303 Operator Interface Terminal combines unique capabilities normally expected from high-end units with a very affordable pri

Page 2 - SpecificationS

21. POWER REQUIREMENTS:+24 VDC ±20% @ 9.5 W maximum.Must use a Class 2 circuit according to National Electrical Code (NEC), NFPA-70 or Canadian Electr

Page 3 - INSERTING KEY STRIPS

3inStalling and powering the g303USER IDENTIFIABLE KEYSThe G303 unit comes with a pre-printed key strip inserted. This key strip is labeled F1 through

Page 4 - G3 RS232 to a PC

4CONFIGURING A G303The G303 is configured using Crimson 2.0 software. Crimson is available as a free download from Red Lion’s website, or it can be or

Page 5 - PROTECTIVE

RS422/485 COMMS PORTThe G303 has one RS422/485 port. This port can be configured to act as either RS422 or RS485.The RS422/485 COMMS and RS232 COMMS p

Page 6 - Software/unit operation

6Software/unit operationFRONT PANEL LEDSThere are three front panel LEDs. Shown below is the default status of the LEDs.1. The operator interface is

Page 7 - BATTERY & TIME KEEPING

7TOPBOTTOMBATTERY & TIME KEEPINGA battery is used to keep time when the unit is without power. Typical accuracy of the G303 time keeping is less t

Page 8 - LIMITED WARRANTY

optional featureS and acceSSorieSCOMPACTFLASH SOCKETCompactFlash socket is a Type II socket that can accept either Type I or II cards. Use cards with